| Specifications |
Voltage Measurements
|
4 fully differentiated channels
100-600Vrms; user selected 0.5-20Vrms on one channel
Accuracy: ±1% reading ± 0.05% full scale |
|
Voltage Transients
|
50-1000Vpk; user selected
1-30Vpk on one channel
1 microsecond minimum duration
Accuracy: ±10% reading ± 1% full scale (requires TaskCard PQLite) |
|
Current Measurement
|
4 fully independent current channels
10 - 200% of full-scale current probe rating
Accuracy: ±1% reading ±0.05% full scale
(at fundamental, plus current probe accuracy) |
|
Current Transients
|
10-300% CT full scale except Chan D 2-200% CT full scale
1 microsecond minimum duration
Accuracy: ±10% reading ±1% full scale plus probe
NOTE: Requires TASKCard PQLite H-T, PQLite H-T-M or H-T-E-M |
|
Frequency
|
Fundamental range 35 - 60 Hz (For frequencies outside the 50-60Hz range, contact the factory before ordering)
Accuracy ±0.2% of reading |
|
Update Rates
|
All parameters updated once per second
(Harmonic-based parameters updated every 5 seconds) |
|
Environment
|
41°F to 113°F
+5°C to +45°C
Humidity 10% - 90% non-condensing |
|
Battery
|
2 hours operation
3 hours full recharge
(continuous operation from battery eliminator) |
|
Certifications
|
CE, FCC, ISO-9001 |
|
|