Specifications for the Power Platform PP-4300

Specifications
Voltage Measurements
  • 4 fully differentiated channels
  • 100-600Vrms; user selected 0.5-20Vrms on one channel
  • Accuracy: ±1% reading ± 0.05% full scale
  • Voltage Transients
  • 50-1000Vpk; user selected
  • 1-30Vpk on one channel
  • 1 microsecond minimum duration
  • Accuracy: ±10% reading ± 1% full scale
    (requires TaskCard PQLite)
  • Current Measurement
  • 4 fully independent current channels
  • 10 - 200% of full-scale current probe rating
  • Accuracy: ±1% reading ±0.05% full scale
  • (at fundamental, plus current probe accuracy)
  • Current Transients
  • 10-300% CT full scale except Chan D 2-200% CT full scale
  • 1 microsecond minimum duration
  • Accuracy: ±10% reading ±1% full scale plus probe
  • NOTE: Requires TASKCard PQLite H-T, PQLite H-T-M or H-T-E-M
  • Frequency
  • Fundamental range 35 - 60 Hz
    (For frequencies outside the 50-60Hz range, contact the factory before ordering)
  • Accuracy ±0.2% of reading
  • Update Rates
  • All parameters updated once per second
    (Harmonic-based parameters updated every 5 seconds)
  • Environment
  • 41°F to 113°F
  • +5°C to +45°C
  • Humidity 10% - 90% non-condensing
  • Battery
  • 2 hours operation
  • 3 hours full recharge
    (continuous operation from battery eliminator)
  • Certifications
    CE, FCC, ISO-9001


    All contents of this website © 2007 Dranetz-BMI. All rights reserved.
    Comments are welcome at webmaster@dranetz-bmi.com.